CGP Electronics DPP-24 Instrukcja Użytkownika Strona 35

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 43
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 34
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-401a352.3.11
GP Dimming Panels
GRAFIK Systems
®
DH
SH HDH
SH
GP36-GP144 Large-Size Panels Wiring Overview
Feed Wiring
TerminalBlock
Load Neutral
Load
DimmedHot/Live
BranchCircuitBreakers
NEC® Class 2/PELV wiring
PowerFeed(Hot/Live)
Varies depending on MB or MLO.
See model numbers page.
Neutral Feed
Varies depending on MB or MLO.
See model numbers page.
Bypass
Jumpers
Do Not
Remove
Typical Load Circuit
Wiring Tips
Wire the GP36-144 similar to wiring a lighting
Distribution Panel:
•Runfeedandloadwiring.Nootherwiringor
assembly required.
•CommonNeutralsarenotpermitted.Runsepa-
rate Neutrals for each load circuit.
The GP36-144 can provide temporary lighting:
•Wireallloads.
•Donotremovethebypassjumpersthatprotect
the Dimming Modules.
•UseBranchCircuitBreakerstoswitchlightson
and off.
Wire Sizes
•FeedWiring:
Panel Feed Wire Sizes
MainLugsOnly Parallel4AWGto500KCMIL(MCM)
200A-400AMainBreakers 1/0AWG(50mm
2
) to 600 KCMIL (MCM)
•DimmedHot/Live:
14 AWG (2.0 mm
2
) to 10 AWG (4.0 mm
2
)
•LoadNeutral:
14 AWG (2.0 mm
2
) to 6 AWG (10.0 mm
2
)
Power Equipment