SPECIFICATION SUBMITTAL
369-401a 23 2.3.11
GP Dimming Panels
GRAFIK Systems
®
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambienttemperature
willbe0-40°C(32-104°F).
•Thisequipmentisaircooled.Donotblockventsorwarranty
will be void. Leave 12 in (310 mm) clearances above, below,
and in front of Panel. Leave clearance on sides for NEC®
Class 2/PELV wiring.
•Reinforcewallstructureforweightandlocalcodes.
Wiring Raceway
Feed
Wiring
air
flow
Load
Circuit
Wiring
Main Lugs or
MainBreaker.
TerminalBlocks
for Load Circuits
12 in
(310 mm)
minimum
top and front
12 in
(30 mm)
minimum
GP8-24 Front View GP8-24 Side View
For maximum Feed and Wire Sizes,
consult Wiring Overview page.
•DimmingPanelswillhumslightlyandinternalrelayswillclick
while in op er a tion. Mount where audible noise is ac cept able.
•MountPanelssoline(mains)voltagewiringisatleast6ft
(1.8 m) from sound or electronic equipment and wiring.
•GPPanelsmustbemountedwithin7°oftruevertical.
NEC® Class 2/
PELV Wiring
GP8-24 Standard-Size Panel Mounting
Panel
GP8
GP12
GP16
GP20
GP24
Maximum
BTUs/Hour
1365
2045
2725
3405
4085
Weight
(withoutpackaging)
115lbs(52kg)
130lbs(59kg)
145lbs(66kg)
160lbs(73kg)
175lbs(80kg)
Notice: Water damages Panels. Install where they will not get wet.